Description
IBC EBX Series 4 KW | 8KW | 10KW | 12KW
High Efficiency Modulating Electric Boiler
Ideal for locations where no fossil fuel (NG/LP) connections or venting are available. Requiring little maintenance, the EBX™ is 100% energy-efficient with no carbon emissions produced.
- Easy set-up for either Set-Point or Outdoor Reset operation
- User friendly interface with plain English
- Outdoor reset capable with outdoor sensor (sold separately)
- Modulating electric elements provide better temp control
- Full modulation control of heating elements (0-100%)
- Built-in 3 speed boiler pump
- Built-in flow sensor and high limit safeties
Maximum Performance
- No greenhouse gas production means zero CO2 emissions.
- 100% efficient
- Dual Titanium heating elements for long life
- Can be used in high temp applications up to 190°F.
Easy To Install and Service
- Top removable for easy element access
- No venting required; no combustion means no greenhouse gas emissions.
- Few moving parts, less servicing required (Only moving part is the pump)
- Compatible with IBC Air Handlers (AHU Series)
- Propylene Glycol compatible
- Low upfront cost / Minimal initial investment
- Flexible installation
- Integrated drain port
- Aligned side supply and return water connections for series multi-unit operation.
- Little infrastructure means low installation cost.
IBC EBX Series Technical Data
SPECIFICATION | EBX 4K-240 | EBX 8K-240 | EBX 10K-240 | EBX 12K-240 |
Power @ 240V | 1.3 – 13.7 MBH | 2.7 – 27.3 MBH | 3.4- 34.1 MBH | 4.3 – 42.7 MBH |
0.4 – 4.0 kW | 0.8 – 8 kW | 1.0 – 10.0 kW | 1.2 – 12.0 kW | |
Power @ 208V | 1.0 – 10.2 MBH | 2.1 – 20.5 MBH | 2.6 – 25.6 MBH | 3.1 – 30.7 MBH |
0.3 – 3 kW | 0.6 – 6.0 kW | 0.8 – 7.5 kW | 0.9 – 9.0 kW | |
Max. Current Draw (w/ pump) @ 240V | 17.6 A | 34.2 A | 42.6 A | 50.9 A |
Max. Current Draw (w/ pump) @ 208V | 15.4 A | 30.0 A | 37.1 A | 44.3 A |
Breaker Size | 30 A | 45 A | 60 A | 70 A |
Copper Wire Size | 10 AWG | 8 AWG | 8 AWG | 6 AWG |
Min. Ambient Temperature | 32°F / 0°C | |||
Max. Relative Humidity (Non-Condensing) | 122°F / 50°C | |||
Max. Ambient Temperature | 90% | |||
Min. Water Temperature | 34°F / 1°C | |||
Max. Water Temperature (Electronic Hi-Limit) | 190°F/ 88°C | |||
Max. Water Temperature Lockout Limit | 210°F/ 99°C | |||
Weight (Empty) | 29 lbs / 13.2 kgs | |||
Min. Boiler Flow Rate | 0.7 USgpm / 2.6 Lpm | 1.4 USgpm / 5.3 Lpm | 1.7 USgpm / 6.4 Lpm | 2.1 USgpm / 8.0 Lpm |
Max. Boiler Flow Rate | 4.2 USgpm / x 16 Lpm | |||
Max. Operating Water Pressure* | 50 psig / 345 kPa | |||
Min. Water Pressure | 8 psig / 55 kPa | |||
Element Construction | Titanium | |||
Boiler ships with a 30 psi Pressure Relief Valve |
BOILER PUMP
Documentation (IBC EBX Series)
Download List of Manuals
↓ EBX Installation & Operating Instruction Manual |
↓ EBX Enginering Submittal |
↓ EBX Parts Breakdown |
Download List of Literature
↓ EBX Sales Brochure |
↓ EBX Sales Specification Sheet |